If the bit Mn in the module status is set it indicates that an error
has occurred in the data logger. Valid is:
M1 = 1: EEPROM error M5 = 1: RTC error
M2 = 1: FLASH error M6 (currently not occupied)
M3 = 1: ADC error
M4 = 1: configuration error M16 (currently not occupied)
channel information (i...i) length = 32 char
<channel type> ASCII 1 char
<channel notation> ASCII 20 char
<data format> ASCII 1 char
<field length> ASCII 1 char
<decimals> ASCII 1 char
<unit> ASCII 6 char
<channel configuration> ASCII 1 char
<type of calculation> ASCII 1 char
Coding <channel type>:
ASCII "0" Empty Channel (EM)
ASCII "1" Analog Input Channel (AI)
ASCII "2" Arithmetic Channel (AR)
ASCII "3" Digital Output Channel (DO)
ASCII "4" Digital Input Channel (DI)
ASCII "5" Setpoint Channel (VO)
ASCII "6" Alarm Channel (AL)
Coding <channel configuration>:
Bit 1: tare/reset possible
Bit 2: average value storage configured